XM31-918-HP
Power Supply
 
 

Alarms
 

Battery
 

Power Supply
Model ALPHA/XM31-918-HP
Firmware V1.02.0
Major Alarm Self test fail: low battery
Minor Alarm OK
Operational Mode Line
Charger Mode Float
Tamper Door closed
Power Supply Language English
Power Supply Priority Normal
Input
AC Line Mode OK
Voltage 125.02 V
Current 5.64 A
Power 539 W
Frequency 60 Hz
Tap Status Normal
Frequency Range 3.00 Hz
Current Limit 17.00 A
Input Power Consumption 0 Wh
Output
Voltage 87.38 V
Power 408 W
Apparent Power 470.10 VA
Frequency 60.04 Hz
Percent Load 29.80 %
Output Setting 90 V
Output Regulation Fine
Over-current Tolerance 3.000 sec
Retry Delay 60 sec
Retry Limit 20
Current 5.38 A
Inverter
Inverter Status Off
End of Discharge Type String
End of Discharge Level 1.75 V/cell
Reduced Peak Mode Disable
Total Standby Events 65
Time Since Last Standby Event 45d 17h:31m
Time in Last Standby Event 0d 0h:01m
Total Time in Standby 587 min
Standby Events Since Reset 28
Time in Standby Since Reset 163 min
Time Since Reset 729 day(s)
Total Run Time 729 day(s)
Transformer Run Time 729 day(s)
Total Downtime 0d 0h:00m
Oil Cap Lifespan Consumed 0.0 %
Self Test
Deep Discharge Cycle Timed
Test Countdown 8 day(s)
Test Duration 10 min
Test Interval 30 day(s)
Test Inhibit No

 